We manufacture a wide range of products to protect against the effects of high altitude detonation of Nuclear devices.

The result of such an event is tHigh Altitude Electromagnectic Pulse Illustrationhe generation of electromagnetic pulses, which induce a high voltage transient in exposed conductors. The resulting EMP may affect several thousands of square kilometres, with a magnitude of tens of kilovolts, and can result in serious damage to insulation, breakdown of semiconductors, and the consequent malfunction of critical equipment such as Energy Power Supply and Communications Systems.

  • From low-voltage telecommunications and signal lines to high-current and voltage installations.
  • From 10v, 5A continuous with a maximum surge current capability of 4.5kA  - (8/20µs), up to and including 500v, 600A continuous, with a 50kA maximum surge.

Products listed below represent just a few of the solutions we offer. If you don't see the asembly or specification you require listed below, please contact our technical team and they will be able to suggest a suitable product that isn't listed, or design a bespoke solution to suit your application.

  • Range of 1 Channel EMP Devices
  • Continuous Operating Voltage 50V to 600V AC rms
  • 4 Active MOV Per Line
  • Repetetive Duty 4/20μs 5000A
  • Max 8/20μs Current per Channel 30000A

ZOMM141/XXX/4/1 Series - A range of robust 1 channel devices to protect equipment against the effects of EMP.  Recommended for Zones 0,1 & 2. Continuous operating voltage 50V to 600V AC rms. Maximum Current per Channel 8/20μs 30000A with a leakage current per channel at rated voltage, DC <200μA. 

  • 12 Channel EMP device
  • 250V AC/325V DCrms
  • 1 Active MOV per line
  • Repetetive Duty 4/20μs 300A
  • Max 8/20μs Current per Channel 4500A

ZOMM108/309/1/12 - 12 channel device to protect equipment against the effects of EMP.  Recommended for Zone 2. Continuous operating voltage AC rms 250V, DC 325V. Maximum Current per Channel 8/20μs 4500A with a leakage current per channel at rated voltage, DC <50μA. 

  • Range of 16 Channel EMP Devices
  • Continuous Operating Voltage 25V to 280V AC rms
  • 1 Active MOV per line
  • Repetetive Duty 4/20μs 300A - 600A
  • Max 8/20μs Current per Channel 1000A - 4500A

ZOMM131/XXX/1/16 Series - A range of 16 channel devices to protect equipment from the effects of EMP.  Recommended for Zone 2. Continuous operating voltage  25V to 280V AC rms. Max Current per Channel 8/20μs 1000A to 4500A and leakage current per channel at rated voltage, DC <100μA

  • Range of 16 Channel EMP Devices
  • 10VAC/12VDC to 120VAC/156VDC rms
  • 1 Active MOV per line
  • Repetetive Duty 4/20μs 300A
  • Max 8/20μs Current per Channel 4500A

ZOMM108/XXX/1/16 Series - A range of 16 channel devices to protect equipment against the effects of EMP.  Recommended for Zone 2. Continuous operating voltage AC rms 10V to 120V &  DC 12V to 156V. Maximum Current per Channel 8/20μs 4500A with a leakage current per channel at rated voltage, DC <50μA

  • Range of 2 Channel EMP Devices
  • Continuous Operating Voltage 110V to 440V AC rms
  • 2 Active MOV Per Line
  • Repetetive Duty 4/20μs 2500A
  • Max 8/20μs Current per Channel 15000A

ZOMM133/XXX/2/2 Series - A range of robust 2 channel devices, recommended for Zones 0,1 & 2, to protect equipment against the effects of EMP. Continuous operating voltage 110V to 440V AC rms . Maximum Current per Channel 8/20μs 15000A with a leakage current per channel at rated voltage, DC <250μA. 

  • Range of 2 Channel EMP Devices
  • Continuous Operating Voltage AC rms 120V to 440V
  • 4 Active MOV Per Line
  • Repetetive Duty 4/20μs 5000A
  • Max 8/20μs Current per Channel 30000A

ZOMM123/XXX/4/2 Series - A range of robust 2 channel devices to protect equipment against the effects of EMP.  Recommended for Zones 0,1 & 2. Continuous operating voltage AC rms 120V to 440V. Maximum Current per Channel 8/20μs 30000A with a leakage current per channel at rated voltage, DC <200μA. 

  • Range of 2 Channel EMP Devices
  • Continuous Operating Voltage 50V to 320V AC rms
  • Continuous current per channel 10A
  • Repetetive Duty 4/20μs 1000A
  • Max 8/20μs Current per Channel 6500A

ZOMM127/XXX/1/2 Series - A range of 2 channel devices to protect equipment against the effects of EMP.  Recommended for Zone 1 (Internal) *Except Ref: 127/400 and 127/401. Continuous operating voltage  50V to 320V AC rms.  Maximum Current per Channel 8/20μs 6500A with a leakage current per channel at rated voltage, DC <100μA

  • Range of 2 Channel EMP Devices
  • Continuous Operating Voltage 50V to 320V AC rms
  • Continuous current per channel 20A
  • Repetetive Duty 4/20μs 1000A
  • Max 8/20μs Current per Channel 6500A

ZOMM127A/XXX/1/2 Series - A range of 2 channel devices to protect equipment against the effects of EMP.  Recommended for Zone 1 (Internal) *Except Ref: 127A/400 and 127A/401. Continuous operating voltage  50V to 320V AC rms.  Maximum Current per Channel 8/20μs 6500A with a leakage current per channel at rated voltage, DC <100μA

  • Range of 2 Channel EMP Devices
  • Continuous Operating Voltage 110V to 250V AC rms
  • 1 Active MOV Per Line
  • Repetetive Duty 4/20μs 600 to 1000AA
  • Max 8/20μs Current per Channel 4500 to 6500A

ZOMM237/XXX/1/2 Series - A range of 2 channel devices to protect equipment against the effects of EMP.  Recommended for Zone 0. Continuous operating voltage 110V to 250V AC rms . Maximum Current per Channel 8/20μs 4500A  to 6500with a leakage current per channel at rated voltage, DC <50μA

  • 20 Channel EMP device
  • 110V AC/145V DCrms
  • 1 Active MOV per line
  • Repetetive Duty 4/20μs 300A
  • Max 8/20μs Current per Channel 4500A

ZOMM 124/303/1/20 - 20 channel device to protect equipment against the effects of EMP.  Recommended for Zone 2. Continuous operating voltage 110V AC rms, 145V DC. Maximum Current per Channel 8/20μs 4500A with a leakage current per channel at rated voltage, DC <50μA

  • Range of 24 Channel EMP Devices
  • Continuous Operating Voltage AC rms 10V to 120V
  • 1 Active MOV Per Line
  • Repetetive Duty 4/20μs 300A
  • Max 8/20μs Current per Channel 1000A

ZOMM124/XXX/1/24 Series - A range of robust 24 channel devices to protect equipment against the effects of EMP.  Recommended for Zone 2. Continuous operating voltage 10V to 120V AC rms and 12V to 156V DC . Maximum Current per Channel 8/20μs 1000A with a leakage current per channel at rated voltage, DC <50μA. 

  • Range of 30 Channel EMP Devices
  • Continuous Operating Voltage AC rms 50V to 280V
  • 1 Active MOV Per Line
  • Repetetive Duty 4/20μs 1500A
  • Max 8/20μs Current per Channel 8000A

ZOMM221/XXX/1/30 Series - A range of robust 30 channel devices to protect equipment against the effects of EMP.  Recommended for Zones 0,1 & 2. Continuous operating voltage AC rms 50V to 280V. Maximum Current per Channel 8/20μs 8000A with a leakage current per channel at rated voltage, DC <200μA. 

  • Range of 33 Channel EMP Devices
  • Continuous Operating Voltage AC rms 20V to 280V
  • 1 Active MOV Per Line
  • Leakage Current Per Channel DC <50μA
  • Max 8/20μs Current per Channel 1000A

ZOMM124/XXX/1/33 Series - A range of robust 33 channel devices to protect equipment against the effects of EMP.  Recommended for Zone 2. Continuous operating voltage 20V to 280V AC rms. Maximum Current per Channel 8/20μs 1000A with a leakage current per channel at rated voltage, DC <50μA. 

  • Range of 4 Channel EMP Devices
  • Continuous Operating Voltage AC rms 50V to 280V
  • 2 Active MOV Per Line
  • Repetetive Duty 4/20μs 2000A
  • Max 8/20μs Current per Channel 10000A

ZOMM205/XXX/2/4 Series - A range of robust 4 channel devices to protect equipment against the effects of EMP.  Recommended for Zones 0, 1 & 2. Continuous operating voltage AC rms 50V to 280V. Maximum Current per Channel 8/20μs 10000A with a leakage current per channel at rated voltage, DC <200μA. 

  • Range of 4 Channel EMP Devices
  • Continuous Operating Voltage 110V to 440V AC rms
  • 2 Active MOV Per Line
  • Repetetive Duty 4/20μs 2500A
  • Max 8/20μs Current per Channel 15000A

ZOMM135/XXX/2/4 Series - A range of robust 4 channel devices to protect equipment against the effects of EMP.  Recommended for Zones 0,1 & 2. Continuous operating voltage 110V to 440V AC rms . Maximum Current per Channel 8/20μs 15000A with a leakage current per channel at rated voltage, DC <250μA. 

  • 4 Channel EMP Device
  • Continuous Operating Voltage AC rms 690V
  • 6 Active MOV Per Line
  • Repetetive Duty 4/20μs 5000A
  • Max 8/20μs Current per Channel 50000A

ZOMM123/3S16/6/4 - A robust 4 channel device to protect equipment against the effects of EMP.  Recommended for Zones 0,1 & 2. Continuous operating voltage AC rms 690V. Maximum Current per Channel 8/20μs 50000A with a leakage current per channel at rated voltage, DC <200μA. 

  • Range of 4 Channel EMP Devices
  • Continuous Operating Voltage AC rms 120V to 440V
  • 4 Active MOV Per Line
  • Repetetive Duty 4/20μs 5000A
  • Max 8/20μs Current per Channel 50000A

ZOMM123/XXX/4/4 Series - A range of robust 4 channel devices to protect equipment against the effects of EMP.  Recommended for Zones 0,1 & 2. Continuous operating voltage AC rms 120V to 440V. Maximum Current per Channel 8/20μs 50000A with a leakage current per channel at rated voltage, DC <200μA. 

  • Range of 4 Channel EMP Devices
  • Continuous Operating Voltage AC rms 50V to 320V
  • 1 Active MOV Per Line
  • Repetetive Duty 4/20μs 1000A
  • Max 8/20μs Current per Channel 6500A

ZOMM127/XXX/1/4 Series - A range of robust 4 channel devices to protect equipment against the effects of EMP.  Recommended for Zone 1 (except ref 400 and 401). Continuous operating voltage AC rms 50V to 320V. Maximum Current per Channel 8/20μs 6500A with a leakage current per channel at rated voltage, DC <100μA. 

  • Range of 4 Channel EMP Devices
  • Continuous Operating Voltage 50V to 320V AC rms
  • Continuous current per channel 20A
  • Repetetive Duty 4/20μs 1000A
  • Max 8/20μs Current per Channel 6500A

ZOMM127A/XXX/1/4 Series - A range of 4 channel devices to protect equipment against the effects of EMP.  Recommended for Zone 1 (Internal) *Except Ref: 127A/400 and 127A/401. Continuous operating voltage  50V to 320V AC rms.  Maximum Current per Channel 8/20μs 6500A with a leakage current per channel at rated voltage, DC <100μA

  • Range of 8 Channel EMP Devices
  • Continuous Operating Voltage AC rms 50V to 280V
  • 2 Active MOV Per Line
  • Repetetive Duty 4/20μs 2000A
  • Max 8/20μs Current per Channel 10000A

ZOMM210/XXX/2/8 Series - A range of robust 8 channel devices to protect equipment against the effects of EMP.  Recommended for Zones 0,1 & 2. Continuous operating voltage AC rms 50V to 280V. Maximum Current per Channel 8/20μs 10000A with a leakage current per channel at rated voltage, DC <200μA. 

  • Range of 8 Channel EMP Devices
  • 10VAC/12VDC to 120VAC/156VDC rms
  • 1 Active MOV per line
  • Repetetive Duty 4/20μs 300A
  • Max 8/20μs Current per Channel 1000A

ZOMM108/XXX/1/8 Series - A range of 8 channel devices to protect equipment against the effects of EMP.  Recommended for Zone 2. Continuous operating voltage AC rms 10V to 120V &  DC 12V to 156V. Maximum Current per Channel 8/20μs 1000A with a leakage current per channel at rated voltage, DC <50μA

  • 8 Channel EMP device
  • 280V AC/350V DCrms
  • 1 Active MOV per line
  • Repetetive Duty 4/20μs 300A
  • Max 8/20μs Current per Channel 4500A

ZOMM 108/310/1/8 - 8 channel device to protect equipment against the effects of EMP.  Recommended for Zone 2. Continuous operating voltage AC rms 280V, DC 350V. Maximum Current per Channel 8/20μs 4500A with a leakage current per channel at rated voltage, DC <50μA

  • Range of 8 Channel EMP Devices
  • 10VAC/12VDC to 120VAC/156VDC rms
  • 2 Active MOV Per Line
  • Repetetive Duty 4/20μs 600A
  • Max 8/20μs Current per Channel 4500A

ZOMM108/XXX/2/8 Series - A range of 8 channel devices to protect equipment against the effects of EMP.  Recommended for Zone 2. Continuous operating voltage AC rms 10V to 120V &  DC 12V to 156V. Maximum Current per Channel 8/20μs 4500A with a leakage current per channel at rated voltage, DC <50μA

  • Range of 8 Channel EMP Devices
  • Continuous operating voltage 50V to 320V AC rms
  • 1 Active MOV Per Line
  • Repetetive Duty 4/20μs 1000A
  • Max 8/20μs Current per Channel 6500A

ZOMM131/XXX/1/8 Series - A range of 8 channel devices to protect equipment against the effects of EMP.  Recommended for Zone 1 * except ref 131/400 and 131/401. Continuous operating voltage 50V to 320V AC rms . Maximum Current per Channel 8/20μs 6500A with a leakage current per channel at rated voltage, DC <100μA